Fluke Networks DSX-8000-MOD 2 GHz DSX Cable Analyzer Module Replacement 1 Unit

$4,051.00
In Stock

Monarch Fluke Networks DSX-8000-MOD operating with a 7.2 V lithium ion battery pack automates advanced structural link data testing within server farming centers via an assertive 2000 MHz maximum frequency spectrum.

  • 16 seconds Category 8 autotest streamlines.
  • 5.7 in touchscreen interface coordinates.
  • 2000 MHz maximum operational frequency analyzes.
  • 1 year factory calibration period secures.
  • 1 m drop resistance rating safeguards.
In Stock
Commercial Pricing
Request for Quotations for Bulk Orders
SKU: Fluke-Networks-DSX-8000-MOD
Brand:

Fluke Networks DSX-8000-MOD 2 GHz DSX Cable Analyzer Module Replacement 1 Unit Specs

Shielded and unshielded pair LAN cablingTIA Category 3, 4, 5, 5e, 6, 6A: 100 Ω   ISO/IEC Class C, D, E, EA, F, and FA: 100 Ω and 120 Ω
Permanent link adaptersPlug type: shielded RJ45   Optional Plug type : Tera (for DSX-5000 only, DSX-8000 version available summer 2017)
Channel AdaptersJack type: shielded RJ45   Optional Jack type: Tera (for DSX-5000 only, DSX-8000 version available summer 2017)
TIACategory 3, 4, 5, 5e, 6, 6A per TIA 568-C.2
ISO/IECClass C and D, E, Ea, F, FA certification per ISO/IEC 11801:2002 and amendments
Maximum frequencyDSX-8000: 2000 MHz
Speed of AutotestFull 2-way Autotest of Category 5e or 6/Class D or E: 7 seconds. Full 2-way Autotest of Category 6A/Class EA: 8 seconds. Full 2-way Autotest of Category 8: 16 seconds
Support test parameters (The selected test standard determines the test parameters and the frequency range of the tests)Wire Map, Length, Propagation Delay, Delay Skew, DC Loop Resistance, Insertion Loss (Attenuation), Return Loss (RL), NEXT, Attenuation-to-crosstalk Ratio (ACR-N), ACR-F (ELFEXT), Power Sum ACR-F (ELFEXT), Power Sum NEXT, Power Sum ACR-N, Power Sum Alien Near End Xtalk (PS ANEXT), Power Sum Alien Attenuation Xtalk Ratio Far End (PS AACR-F)
Input protectionProtected against continuous telco voltages and 100 mA over-current. Occasional ISDN over-voltages will not cause damage
Display5.7 in LCD display with a projected capacitance touchscreen
CaseHigh impact plastic with show absorbing overmold
DimensionsMain Versiv unit with DSX module and battery installed: 2.625 in x 5.25 in x 11.0 in (6.67 cm x 13.33 cm x 27.94 cm)
WeightMain Versiv unit with DSX module and battery installed: 3 lbs, 5oz (1.28 kg)
Main unit and remoteLithium ion battery pack, 7.2 V
Typical battery life8 hours
Charge time*Tester off: 4 hours to charge from 10 % capacity to 90 % capacity.
Languages supportedEnglish, French, German, Italian, Japanese, Portuguese, Spanish, Chinese, Korean, Russian, Trad Chinese, Czech, Polish, Swedish, Hungarian
CalibrationService center calibration period is 1 year
Operating Temperature32°F to 113°F (0°C to 45°C)
Storage Temperature-4°F to +122°F (-20° C to +50°C)
Operating relative humidity0 % to 90 %, 32°F to 95 °F (0°C to 35°C)   0 % to 70 %, 95°F to 113 °F (35°C to 45°C)
VibrationRandom, 2 g, 5 Hz-500 Hz
Shock1 m drop test with and without module and adapter
SafetyCSA 22.2 No. 61010, IEC 61010-1 2nd Edition + Amendments 1, 2
Operating altitude13,123 ft (4,000 m)   10,500 ft (3,200 m) with ac adapter
EMCEN 61326-1
Category 8 test modes (or lower link categories)ANSI/TIA-1152 Level 2G
Class I/II test modesProposed standard IEC 61935-1 Ed. 5 Level VI
Without RemoteWith Remote
Range800 m (2600 ft)
Resolution0.1 m or 1 ft
Accuracy ±(0.3 m + 2 %); 0 m to 150 m   ± (0.3 m + 4 %); 150 m to 800 m
Without RemoteWith Remote
Range4000 ns
Resolution1 ns
Accuracy± (2 ns + 2 %); 0 ns to 750 ns   ± (2 ns + 4 %); 750 ns to 4000 ns
Range0 ns to 100 ns
Resolution1 ns
Accuracy± 10 ns
Range0 Ω to 540 Ω
Resolution0.1 Ω
Accuracy± (1 Ω + 1 %)
Overload recovery timeLess than 10 minutes to rated accuracy following an overvoltage. Referencing is required after repeated or prolonged overvoltage.

Reviews

There are no reviews yet.

Be the first to review “Fluke Networks DSX-8000-MOD 2 GHz DSX Cable Analyzer Module Replacement 1 Unit”

Your email address will not be published. Required fields are marked *