Fluke 1746/15/EUS Three-Phase Power Quality Loggers Specs

ParameterRange
Voltage1000 V
Current: Direct inputi17xx-flex 1500IP 24 1500 A
1500 A0.1 A
i17xx-flex 3000IP 24 3000 A300 A
3000 A0.1 A
i17xx-flex 6000IP 36 6000 A600 A
6000 A0.1 A
i40s-EL clamp4 A
40 A10 mA
Frequency42.5 Hz to 69 Hz
Auxiliary input±10 V dc
Voltage min/max1000 V
Current min/maxDefined by accessory
THD on voltage1000%
THD on current1000%
Voltage harmonics 2nd to 50th1000 V
Current harmonics 2nd to 50thDefined by accessory
Flicker PLT, PST0 to 20
ParameterInfluence quantity
150 A / 1500 A300 A / 3000 A
Active Power PPF ≥ 0.99
Apparent power SPF ≥ 0.99
Reactive power Q0 ≤ PF ≤ 1
Reactive power Q0 ≤ PF ≤ 1
Power Factor PF-
Additional uncertainty in% of rangeVP-N>250 V
Voltage range100 V to 500 V using safety plug input when powering from the measurement circuit
Power consumptionMaximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency≥ 68.2 % (in accordance with energy efficiency regulations)
Maximum no-load consumption< 0.3 W only when powered using IEC 60320 input
Mains power frequency50/60 Hz ± 15 %
BatteryLi-ion 3.7 V, 9.2 Wh, customer-replaceable
On-battery runtimeTypically 4 hours
Charging time< 6 hours
Resolution16-bit synchronous sampling
Sampling frequency10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency50/60 Hz (42.5 to 69 Hz)
Circuit types1-φ, 1-φ IT, split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, currents only (load studies)
Data storageInternal flash memory (not user replaceable)
Memory sizeTypical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Measured parametersVoltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging intervalUser selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max valuesVoltage, current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC 61000-4-30 Aux, Power: 200 ms)
Measured parametersEnergy (Wh, varh, VAh), PF, maximum demand, cost of energy
IntervalUser selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Measured parameterVoltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
Averaging interval10 min for all parameters   2 hrs (long term Flicker PLT)   150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Individual harmonics2nd to 50th harmonic   Grouping according to IEC 61000-4-7 user configurable depending on application:   Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
Interharmonics1st to the 50th interharmonic
Total harmonic distortionCalculated on 50 voltage harmonics
EventsVoltage: dips, swells, interruptions, current: inrush current   1748: mains signaling, transients (low frequency)
Triggered recordingsRMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s   (URMS1/2 according to IEC 61000-4-30)   Waveform of voltage and current up to 200 ms, 10/12 cycles   Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s
InrushRMS profile based on 1/2 cycle RMS steady state triggering
FlickerIn accordance with IEC 61000-4-15 and IEEE 1453
Mains signalingTwo user defined frequencies up to 3 kHz
PQ HealthSummarizes power quality measurements in one table. Detailed data available for each parameter
EN 50160Compliance with standard
Programmable PQ limitsEnables user defined limits for local standards compliance
HarmonicsIEC 61000-4-7: Class 1
Power qualityIEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
PowerIEEE 1459
Power quality complianceEN 50160
SafetyGeneral: IEC 61010-1: Pollution Degree 2   Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V   Power Supply: Overvoltage Category IV, Pollution Degree 2   Li-ion Battery: IEC 62133
USB-AFile transfer via USB flash drive, firmware updates, max. supply current: 120 mA
WiFiFile transfer and remote control via direct connection or WiFi infrastructure
BluetoothRead auxiliary measurement data from Fluke Connect ® 3000 series modules   (requires supported USB to BLE or WiFi/BLE adapter, check for availability)
USB-mini-BData download device to PC
Number of inputs4 (3 phases referenced to neutral)
Maximum input voltage1000 Vrms, CF 1.7
Input impedance10 MΩ
Bandwidth42.5 Hz to 3.5 kHz
Scaling1:1 and variable
Measurement category1000 V CAT III/600 V CAT IV
Number of inputs4 (3 phases and neutral), mode selected automatically for attached sensor
Input voltageClamp input: 500 mVrms/50 mVrms; CF 2.8   Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range
Range1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24"   3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24"   6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36"   40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth42.5 Hz to 3.5 kHz
Scaling1:1 and variable
Number of inputs2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input range0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s
Scale factorFormat: mx + b (gain and offset) user configurable
Displayed unitsUser configurable (7 characters, for example, °C, psi, or m/s)
Number of inputs2
Supported modulesFluke Connect ® 3000 series
Acquisition1 reading/s
Operating temperature-25 °C to +50 °C (-13 °F to 122 °F)1
Storage temperatureWithout battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F)
Operating humidityIEC 60721-3-3: 3K6:   -25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 %   40 °C (104 °F): 55 %   50 °C (122 °F): 35 %
Operating altitude2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude12,000 m
EnclosureIEC 60529: IP50   IEC 60529: IP65 with IP65 rated voltage connector
VibrationIEC 60721-3-3 / 3M2
Electromagnetic compatibility (EMC)EN 61326-1: Industrial CISPR 11: Group 1, Class A   IEC 61000-6-5 Power station environment   Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)   USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Features1742
Voltage, current, power, power factor, frequency
Energy forward/reverse
Peak Demand
THD
Flicker
Voltage and current harmonics (to 50th)1
Unbalance1
Rapid voltage change events1
Interharmonics (to 50th)1
Dips, swells, interruption and transient events tables1
Inrush current1
Transients (low frequency)/Waveform deviation events2
Trend
Waveform snapshots2
RMS profile2
Ethernet
USB (mini B)
WiFi download Instrument to device
Wifi download via WiFi hub (requires registration)Opt.
Flexible current probenot /B version
USB stick
USB cable
3PHVL-1730 3-Phase + neutral voltage test lead
Test lead set red/black 0.18 m
     
  • 24IN/60CM 1,500A IFLEX, EUS Version - IP65 Rated
  •  
  • USB stick
  •  
  • USB cable
  •  
  • 3PHVL-1730 3-Phase + neutral voltage test lead
  •  
  • Test lead set red/black 0.18 m
  •  
  • Test lead set red/black 1.5 m
  •  
  • 4 Alligator clips
  •  
  • 173x/174x Soft Case
  •  
  • Cable marker kit
  •  
  • MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black)