Fluke 1775 - Three-Phase Power Quality Analyzer Specs
| Number of inputs | 4 inputs, 3 phases and neutral referenced to PE (5 connectors) |
| Measurement category | 1000 V CAT III / 600 V CAT IV |
| Maximum input voltage | 1000 V rms / 1000 V dc (1700 Vpk) Nominal voltage range Wye and single phase: variable (50 V - 1000 V) Delta: Variable (100 V - 1000 V) IEC 61000-4-30 Class A compliance for the nominal voltages (Vdin) 100 V - 690 V |
| Input impedance | 10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE |
| Bandwidth | DC to 30 kHz for PQ measurements, excluding transients |
| Resolution | 24-bit synchronous sampling |
| Sampling frequency | 80 kS/s at 50/60 Hz |
| Scaling | 1:1, variable for use of potential transformers |
| Measurement range | ±8 kV |
| Sampling rate | 1775: 1 MS/s |
| Bandwidth | DC to 1 MHz |
| Trigger | Adjustable trigger level. Triggers on high-frequency components > 1.5 kHz |
| Resolution | 14-bit synchronous sampling |
| Number of inputs | 4 inputs 3 phases and Neutral, range selected automatically to attached sensor |
| Range | AC |
| DC | 20 A to 2000 A with 80i-2010-EL clamp |
| Bandwidth | DC to 30 kHz |
| Resolution | 24-bit synchronous sampling |
| Sampling frequency | 80 kS/s at 50/60 Hz |
| Scaling | 1:1, variable |
| Input voltage | Clamp: 50 mV / 500 mV rms; CF 2.8 Rogowski Coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz CF 4 all at nominal probe range |
| Input impedance | 11 kΩ |
| Power | IEEE 1459 |
| Harmonics | IEC 61000-4-7: Class 1 IEEE 519 (short time and very short time harmonics) |
| Flicker | IEC 61000-4-15 Class F1 |
| Power quality | IEC 61000-4-30 Class A, IEC 62586 PQI-A-PI |
| Power quality compliance | EN 50160 + GOST + NEQUAL + NETCODE + FOL |
| Ethernet | 1 Gbit/s 1000BASE-T |
| USB type A | USB 2.0 high speed for USB flash drives to transfer measurement data, firmware updates and license installation. Max. supply current: 500 mA |
| USB-C | USB 2.0 high speed for data download to PC and calibration (requires USB type A to USB-C or USB-C to USB-C cable) Auxiliary power supply for the Analyzer (requires USB C power adapter PD 2.0 or higher with 9 V 1.8 A support) USB 3.0 super-speed for USB-C flash drives to transfer measurement data, firmware updates and license installation. Max. supply current: 900 mA |
| WiFi/BLE module1 | 802.11 ac 2.4 GHz / 5 GHz, support for concurrent access point and client mode Bluetooth 5.0/BLE Antenna: Internal and external2 |
| LTE/4G module3 | LTE-A Cat 12 Worldwide LTE-A and UMTS/HSPA+ coverage Antenna: External2 |
| GPS | MCX connector to attach a GNSS antenna for GPS/GLONASS2 |
- FLUKE-1775 Power Quality Analyzer
- I17XX-FLEX1500/18 (set of four)
- FLUKE-17XX Flat Cable Voltage Test Lead 3-Phase N
- AC285 Black Alligator Clips (set of four)
- Black 1m USB-C Cable
- Line Cord
- FLK-17XX 0.18M Test Lead Set
- Green Test Lead
- MP1-3R/1B Magnet Probe Set
- FLUKE-174X-HANGER Magnetic Hanging Kit
- FLUKE-177X-4204, WI-FI/BLE Module
- Cable Marker Set (for Voltage and Current)
- FLUKE-174X-MA-C8 Wall Outlet Adapter
- Black Soft Case