Fluke 1775 - Three-Phase Power Quality Analyzer Specs

Number of inputs4 inputs, 3 phases and neutral referenced to PE (5 connectors)
Measurement category1000 V CAT III / 600 V CAT IV
Maximum input voltage1000 V rms / 1000 V dc (1700 Vpk) Nominal voltage range Wye and single phase: variable (50 V - 1000 V)   Delta: Variable (100 V - 1000 V)   IEC 61000-4-30 Class A compliance for the nominal voltages (Vdin) 100 V - 690 V
Input impedance10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE
BandwidthDC to 30 kHz for PQ measurements, excluding transients
Resolution24-bit synchronous sampling
Sampling frequency80 kS/s at 50/60 Hz
Scaling1:1, variable for use of potential transformers
Measurement range±8 kV
Sampling rate1775: 1 MS/s
BandwidthDC to 1 MHz
TriggerAdjustable trigger level. Triggers on high-frequency components > 1.5 kHz
Resolution14-bit synchronous sampling
Number of inputs4 inputs 3 phases and Neutral, range selected automatically to attached sensor
RangeAC
DC20 A to 2000 A with 80i-2010-EL clamp
BandwidthDC to 30 kHz
Resolution24-bit synchronous sampling
Sampling frequency80 kS/s at 50/60 Hz
Scaling1:1, variable
Input voltageClamp: 50 mV / 500 mV rms; CF 2.8   Rogowski Coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz   CF 4 all at nominal probe range
Input impedance11 kΩ
PowerIEEE 1459
HarmonicsIEC 61000-4-7: Class 1   IEEE 519 (short time and very short time harmonics)
FlickerIEC 61000-4-15 Class F1
Power qualityIEC 61000-4-30 Class A, IEC 62586 PQI-A-PI
Power quality complianceEN 50160 + GOST + NEQUAL + NETCODE + FOL
Ethernet1 Gbit/s 1000BASE-T
USB type AUSB 2.0 high speed for USB flash drives to transfer measurement data, firmware updates and license installation. Max. supply current: 500 mA
USB-CUSB 2.0 high speed for data download to PC and calibration (requires USB type A to USB-C or USB-C to USB-C cable)   Auxiliary power supply for the Analyzer (requires USB C power adapter PD 2.0 or higher with 9 V 1.8 A support)   USB 3.0 super-speed for USB-C flash drives to transfer measurement data, firmware updates and license installation. Max. supply current: 900 mA
WiFi/BLE module1802.11 ac 2.4 GHz / 5 GHz, support for concurrent access point and client mode   Bluetooth 5.0/BLE   Antenna: Internal and external2
LTE/4G module3LTE-A Cat 12   Worldwide LTE-A and UMTS/HSPA+ coverage   Antenna: External2
GPSMCX connector to attach a GNSS antenna for GPS/GLONASS2
  • FLUKE-1775 Power Quality Analyzer
  • I17XX-FLEX1500/18 (set of four)
  • FLUKE-17XX Flat Cable Voltage Test Lead 3-Phase N
  • AC285 Black Alligator Clips (set of four)
  • Black 1m USB-C Cable
  • Line Cord
  • FLK-17XX 0.18M Test Lead Set
  • Green Test Lead
  • MP1-3R/1B Magnet Probe Set
  • FLUKE-174X-HANGER Magnetic Hanging Kit
  • FLUKE-177X-4204, WI-FI/BLE Module
  • Cable Marker Set (for Voltage and Current)
  • FLUKE-174X-MA-C8 Wall Outlet Adapter
  • Black Soft Case