Fluke 1662 SCH Installation Tester with Memory (SCHUKO) Specs

Model1662
Insulation-PreTest ™ safety function NEW•
Insulation at L-N, L-PE, N-PE inputs NEW•
Auto Test sequence NEW•
Loop and line resistance—mΩresolution•
Continuity at L-N, L-PE, N-PE inputs NEW•
Test smooth dc sensitive RCDs (Type B/B+)•
Earth resistance•
Voltage trms (ac and dc) and frequency•
Wiring polarity checker, detects broken PE and N wires•
Insulation resistance•
Continuity and resistance•
Measure motor windings with continuity test (@ 10 mA)•
Loop and line resistance•
Prospective Earth Fault Current (PEFC/IK)•
Prospective Short-Circuit Current (PSC/IK)•
RCD trip time•
RCD trip current (ramp test)•
Measures trip time and current for RCD type A and AC in one test•
RCD variable test current•
Automatic RCD test sequence•
Phase sequence test•
Fluke Connect ® compatibility NEW•
ShareLive ™ calling NEW•
Fluke Cloud ™ storage NEW•
On/Off switchable Auto Start for RCD and Looptest NEW•
Self-test•
Illuminated display•
Z Max memory NEW•
Memory•
IR-USB and BLE interface (use with optional Fluke DMS software and FVF)IR-USB
Heavy duty mains cord with single input connector NEW•
Hard case•
Remote control probe•
Zero adapter•
SpecificationCharacteristic
Size10 cm (L) x 25 cm (W) x 12.5 cm (H)
Weight (incl. batteries)approx. 1.3 kg
Battery size, quantity1.5 V type AA (IEC LR6), 6 pcs.
SealingIP 40
SafetyComplies with IEC/EN61010-1, UL61010, ANSI/ISA –s82.02.01 and   CAN/CSA c22.2 No. 1010
OvervoltageCAT III 500 V, CAT IV 300 V
PerformanceEC/EN61557-1 to IEC/EN61557-7 and IEC/EN61557-10
RangeResolution
500 V0.1 V
Range (Autoranging)Resolution
20 Ω/200 Ω/2000 Ω0.01 Ω/0.1 Ω/1 Ω
16621663/1664 FC
100-250-500-1000 V50-100-250-500-1000 V
Test VoltageInsulation Resistance Range
50 V20 MΩ/50 MΩ
100 V20 MΩ/100 MΩ
250 V20 MΩ/200 MΩ
500 V20 MΩ/200 MΩ/500 MΩ
1000 V20 MΩ/200 MΩ/1000 MΩ
Insulation safety pretestRequires to connect the Tester to L, N and PE.
RangeResolution
10 Ω(Hi current mΩmode)/20 Ω/200 Ω/2000 Ω1 mΩ/ 0.01 Ω/ 0.1 Ω/1Ω
RangeResolution
1000 A/10 kA (50 kA)1 A/0.1 kA
RCD TypeModel 1662
AC1G2, S3
Current Settings1Multiplier
RCD Type GRCD Type S
10-30-100-300-500-1000 mA – VARx ½, x 1
10-30-100 mAx 5
Current RangeStep Size
Type GType S
30 % to 110 % of RCD rated current110 % of I ▵N 2
Notes   30 % to 210 % for Type A I▵N = 10mA   20 % to 210 % for Type BSpecified trip current ranges (EN 61008-1):   50 % to 100 % for Type AC   35 % to 140 % for Type A (>10 mA)   35 % to 200 % for Type A (=10 mA)   50 % to 200 % for Type B
RangeResolution
200 Ω/2000 Ω0.1 Ω/1Ω
IconRange
Phase Sequence indicator is active100 to 500 V
     
  • 6x AA (IEC LR6) cell batteries
  •  
  • C1600 hard carrying case
  •  
  • Zero adapter
  •  
  • Heavy duty mains cord
  •  
  • STD standard test lead set
  •  
  • C1600 hard carrying case
  •  